Technical data Proline Prowirl 73
90 Endress+Hauser
Support
Stainless steel, 1.4308 (CF8)
Seals
•Graphite
Pressure rating PN 10 to 40, Class 150 to 300, JIS 10 to 20K:
Sigraflex Foil Z (BAM-tested for oxygen applications)
Pressure rating PN 63 to 160, Class 600, JIS 40K:
Sigraflex Hochdruck

with stainless steel sheet reinforcement made of 316(L) (BAM-tested
for oxygen applications, "high quality in terms of TA Luft (German Clean Air Act)"
•Viton
Kalrez 6375
Gylon (PTFE) 3504 (BAM-tested for oxygen applications, "high quality in terms of TA Luft
(German Clean Air Act)"
10.1.12 Human interface
Display elements Liquid crystal display, double-spaced, plain text display, 16 characters per line
Display can be configured individually, e.g. for measured variables and status variables, totalizers
Operating elements Local operation with three keys (O, S, F)
Quick Setup for quick commissioning
Operating elements accessible also in Ex zones
Remote operation Operation via:
HART protocol
FieldCare (software package from Endress+Hauser for complete configuration, commissioning
and diagnosis)