Technical data Proline Prowirl 73
82 Endress+Hauser
10.1.5 Power supply
Electrical connection ä 25
Supply voltage Non-Ex: 12 to 36 V DC (with HART: 18 to 36 V DC)
Ex-i/IS and Ex-n: 12 to 30 V DC (with HART 18 to 30 V DC)
Ex-d/XP: 15 to 36 V DC (with HART: 21 to 36 V DC)
Cable entry Power supply and signal cables (outputs):
Cable entry M20 1.5 (6 to 12 mm / 0.24 to 0.47")
Cable entry M20 1.5 for armored signal cable (9.5 to 16 mm / 0.37 to 0.63")
Thread for cable entry: ½" NPT, G ½", G ½" Shimada
Cable specification Permitted temperature range:
Standard cable: –40 °C (–40 °F) to max. permissible ambient temperature plus 10 °C (18 °F)
Armored cable: –30 to +70 °C (–22 to +158 °F)
Remote version ä 27
Power supply failure Totalizer stops at the last value determined.
All settings are kept in the EEPROM.
Error messages (incl. value of operated hours counter) are stored.
10.1.6 Performance characteristics
Reference operating
conditions
Error limits following ISO/DIN 11631:
20 to 30 °
C (+68 to +86 °F)
•2 to 4 bar (29 to 58 psi)
Calibration rig traced to national standards.
Calibration with the process connection corresponding to the particular standard.
Maximum measured error Volume flow (liquid):
< 0.75% o.r. for Re > 20 000
< 0.75% o.f.s for Re between 4000 and 20 000
Volume flow (gas/steam):
< 1% o.r. for Re > 20 000 and v < 75 m/s (246 ft/s)
< 1% o.f.s for Re between 4000 and 20 000
Temperature:
< 1 °C (T > 100 °C / 212 °F, saturated steam and for liquids at ambient temperature);
< 1% o.r. [K] (gas)
Rise time 50% (agitated under water, following IEC 60751): 8 s
Mass flow (saturated steam):
For flow velocities v = 20 to 50 m/s (66 to 164 ft/s), T > 150 °C / 302 °F (423 K)
< 1.7% o.r. (2% o.r. for remote version) for Re > 20 000
< 1.7% o.f.s (2% o.f.s for remote version) for Re between 4000 and 20 000
For flow velocities v = 10 to 70 m/s (33 to 230 ft/s), T > 140 °C / 284 °F (413 K)
< 2% o.r. (2.3% o.r. for remote version) for Re > 20 000
< 2% o.f.s (2.3% o.f.s. for remote version) for Re between 4000 and 20 000
Mass flow of superheated steam and gas (air, natural gas AGA NX-19, AGA8-DC92,
ISO 12213-2, AGA8 Gross Method 1, SGERG-88, preprogrammed gases – does not apply to the
real gas equation):
!
Note!
A Cerabar S device has to be used for the measuring errors listed below. The measured error used
to calculate the error in the measured pressure is 0.15%.
< 1.7% o.r. (2.0% o.r. for remote version) for Re > 20 000 and
process pressure < 40 bar abs (580 psi abs)