EasyManua.ls Logo

Endress+Hauser Promag 53 - Page 102

Endress+Hauser Promag 53
177 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Commissioning Promag 53 PROFIBUS-DP/-PA
102 Endress+Hauser
Example 4:
Full configuration using the Profile GSD files PA039741.gsd (RS 485) and
PA139741.gsd (IEC 61158-2):
This form of configuration transfers the volume flow - totalizer 1 and the mass flow with
control variable.
Note:
This GSD file contains two AI blocks and a Totalizer block.
The first AI block is always assigned to the volume flow. This guarantees that the first
measured variable agrees with the field equipment of other manufacturers.
The second AI block can be freely selected as Promag 53 is capable of producing a
calculated mass flow.
Note:
There is no difference between the block ID's of the two Profile GSD files PA039741.gsd
(RS 485) and PA139741.gsd (IEC 61158-2).
There is, however, a difference in the baud rates that are supported and the
Min_Slave_Interval.
F06-53PBxxxx-20-xx-xx-xx-003
Slot 0 AI volume flow
Slot 2
Totalizer 1 + Control variable (SET_TOT, MODE_TOT)
Slot 1
AI mass flow
Configuration data
Byte
length
(Input)
Byte
length
(Out-
put)
Data
blocks
Status Access
type
GSD
block
designation
GSD
Extended
block
identifica-
tion
GSD
Standard
block
identifica-
tion
0...4 Volume
flow
+Status
active read AI 0x94
5...9 0...1 Totalizer 1
+ Status
+ Control
active read +
write
SETTOT_
MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85
10...14 Mass flow
+ Status
active
read
AI 0x94

Table of Contents

Related product manuals