Promag 53 PROFIBUS-DP/-PA 6 Commissioning
Endress+Hauser 101
Example 3:
Configuration of the measured variables without placeholders (EMPTY_MODULE) using
the manufacturer-specific GSD file.
This form of configuration transfers the volume flow - totalizer 1 with control variable
(SET_TOT).
Note:
If no further measured variables are required, the placeholders will not have to be used.
This only applies if no manufacturer-specific control blocks are used.
F06-53PBxxxx-20-xx-xx-xx-001
Slot 0: AI volume flow
Slot 1: Totalizer 1 + Control variable (SET_TOT)
Configuration data
Byte
length
(Input)
Byte
length
(Out-
put)
Data
blocks
Status Access
type
GSD
block
designation
GSD
Extended
block
identifica-
tion
GSD
Standard
block
identifica-
tion
0...4 – Volume
flow
+ Status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
5...9 0 Totalizer 1
+ Status
+ Control
variable
active read
+write
SETTOT_
TOTAL
0xC1, 0x80,
0x84, 0x85
0xC1, 0x80,
0x84, 0x85