4) LINEAR INPUT TYPE
The display will show "IN" preceded by:
Push or pushbuttons to set the desired range.
Push the F pushbutton to memorize the new choice and go to the
next parameter.
4.a) SQUARE ROOT EXTRACTION
The display will show "SR" preceded by:
no = square root disabled
YES = square root enabled
Push or pushbuttons to set the desired solution.
Push the F pushbutton to memorize the new choice and go to the
next parameter.
NOTE: If square root extraction is selected, the initial and final
scale readouts must not be negative.
4.b) DECIMAL POINT POSITION
The display will show "dP" preceded by:
- - - -. = no decimal figure
- - -.- = one decimal figure
- -.- - = two decimal figures
-.- - - = three decimal figures
Push or pushbuttons to set the desired position.
Push the F pushbutton to memorize the new position and go to the
next parameter.
4.c) INITIAL SCALE READOUT
The display will show "LR" preceded by a number between -1999
and 9999 .
This step allows to assign a readout value to the initial range value.
Push or pushbuttons to set the desired value (when the
square root extraction is selected, the value must be positive).
Push the F pushbutton to memorize the new value and go to the
next parameter.
4.d) FINAL SCALE READOUT
The display will show "HR" preceded by a number between -1999
and 9999 .
Push or pushbuttons to set the desired value (when the
square root extraction is selected, the value must be positive).
Push the F pushbutton to memorize the new value and go to the
next parameter.
0.20 = 0-20 mA
4.20 = 4-20 mA
0.60 = 0 - 60 mV
12.60 = 12 - 60 mV
0.5 = 0 - 5 V
1.5 = 1 - 5 V
0.10 = 0 - 10 V
2.10 = 2 - 10 V