35
B) The low limit of the input break point is 0.01 more than the
previous input break point while the upper limit is 99.99.
5) DIGITAL FILTER ON READOUT VALUES
The display will show "FILt" followed by a number.
Using ▲ and ▼ pushbutton it is possible to select the desired time
constant for the digital filter in order to obtain a stable readout in
pre-sence of noise also. The possible choices are 0.4, 1, 2, 3, 4 or
5 s.
Push the F pushbutton to memorize the new choice and go to the
parameter 7.
NOTE: this filter is disabled for the instruments with frequency
input.
6) FREQUENCY SETTING
The DPS with frequency input is not jet available so that all the
informations related with frequency input setting are skipped.
7) EXTERNAL CONTACT FUNCTION
This step allows to select the function enabled and disabled by the
external contact.
The display will show "EX" preceded by:
"HOLd" = sampling stop and the instrument maintains the
actual displayed value while the eng. unit will
flash.
"n.RES" = manual reset of the alarms.
Push ▲ or ▼ pushbuttons and set the desired function.
Push the F pushbutton to memorize the new choice and go to the
next parameter.
7.a) CONTACT STATUS
With this parameter is possible to define the external contact status
for function enabling.
The display will show "EX" preceded by:
"CLSd" = enabled with closed contact.
"OPEn" = enabled with open contact.
Push ▲ or ▼ pushbuttons and set the desired status.
Push the F pushbutton to memorize the new status and go to the
next parameter.
Readout
Input