630791 DS MKII INSTALLATION MANUAL
C5
NOTE: Internal install is only recommended for situaons where an external install
is impraccal. For informaon regarding an external install, go to secon C4 on
page 17.
The Universal Vercal Powerue (UVP) internal conguraon is designed to have the
fan, mounted within the roof space of the house, and the vercal 225 mm diameter
liner, containing a 100 mm exi, penetrate through the roof. The UVP internal
conversion kit comes with a 1200 mm liner that is specic to the internal installaon
and must always be used.
NOTE: The ue setup must comply with either secon C1 on page 13 or C2 on
page 14.
Use standard methods to ash the roof penetraon. The installaon must be
weatherproof and conform to all local council standards including powered ue
terminaon rules.
Mount the fan mount bracket (1) to the roof framing and strapping using mber
ensuring that the ue is rigid and vercal. Ensure that the mounng mber does not
obstruct access to the 3xM5 screw threads on the side of the fan unit.
Aim to have the fan enclosure (2) mounted as high as possible, mainly to allow sucient
fall for condensaon drainage if the exi-ue is to run horizontally.
Ensure there is sucient space below fan enclosure (2) to have access to t the exi-
ue tubes (3) and allow owing bends if required.
Ensure the 43 mm restricon plate is installed on the inlet.