630791 DS MKII INSTALLATION MANUAL
Gas Type
Natural Gas ULPG Propane
Minimum Inlet Pressure - Pre-Regulator 1.13 kPa 2.75 kPa 2.75 kPa
Maximum Inlet Pressure - Pre-Regulator 5.00 kPa 5.00 kPa 5.00 kPa
Operang Pressure - Post-Regulator (Point A) 1.00 kPa 2.30 kPa 2.30 kPa
Operang Pressure on
High - (Point B)
DS1150
0.68 kPa ±5 % 1.8 kPa ±5 % 1.8 kPa ±5 %
DS1400
0.82 kPa ±5 % 1.98 kPa ±5 % 1.68 kPa ±5 %
DS1650
0.67 kPa ±5 % 1.67 kPa ±5 % 1.67 kPa ±5 %
Operang Pressure on
Low - (Point B)
DS1150
0.30 kPa ±5 % 0.90 kPa ±5 % 0.90 kPa ±5 %
DS1400
0.40 kPa ±5 % 0.93 kPa ±5 % 1.04 kPa ±5 %
DS1650
0.34 kPa ±5 % 0.82 kPa ±5 % 0.82kPa ±5 %
While the remote is in its “OFF” mode with only the me showing on the display, use the service-mode login
to enter gas er sengs. Tap “Gas adjustment”. Follow the on screen prompts to start the re in gas seng
adjust mode. Fireplace must be connected to the APP (see secon D2).
S4
The high seng for the currently set gas type is displayed rst. Pressing the ‘ ’ or ‘ ’ keys will change the
seng up or down, respecvely, which will change the gas pressure measured at point B.
NOTE: The numbers displayed on the APP should only be used to achieve the correct pressure. The numbers by
themselves do not represent anything and should not be relied upon.