630791 DS MKII INSTALLATION MANUAL

Gas Type
Natural Gas ULPG Propane
Minimum Inlet Pressure - Pre-Regulator 1.13 kPa 2.75 kPa 2.75 kPa
Maximum Inlet Pressure - Pre-Regulator 5.00 kPa 5.00 kPa 5.00 kPa
Operang Pressure - Post-Regulator (Point A) 1.00 kPa 2.30 kPa 2.30 kPa
Operang Pressure on
High - (Point B)
DS1150
0.68 kPa ±5 % 1.8 kPa ±5 % 1.8 kPa ±5 %
DS1400
0.82 kPa ±5 % 1.98 kPa ±5 % 1.68 kPa ±5 %
DS1650
0.67 kPa ±5 % 1.67 kPa ±5 % 1.67 kPa ±5 %
Operang Pressure on
Low - (Point B)
DS1150
0.30 kPa ±5 % 0.90 kPa ±5 % 0.90 kPa ±5 %
DS1400
0.40 kPa ±5 % 0.93 kPa ±5 % 1.04 kPa ±5 %
DS1650
0.34 kPa ±5 % 0.82 kPa ±5 % 0.82kPa ±5 %

While the remote is in its “OFF” mode with only the me showing on the display, use the service-mode login
to enter gas er sengs. Tap “Gas adjustment. Follow the on screen prompts to start the re in gas seng
adjust mode. Fireplace must be connected to the APP (see secon D2).
S4

The high seng for the currently set gas type is displayed rst. Pressing the ‘ ’ or ‘ ’ keys will change the
seng up or down, respecvely, which will change the gas pressure measured at point B.
NOTE: The numbers displayed on the APP should only be used to achieve the correct pressure. The numbers by
themselves do not represent anything and should not be relied upon.