630791 DS MKII INSTALLATION MANUAL
E6.5
Room fan current too low.
Check that room fans and capacitors are plugged in.
E6.6
Room fan current too high.
Check that room fans are not stalled or jammed.
Check wiring loom for damage.
E7.1
Pressure switch stuck closed
at startup
Ensure the pressure switch is mounted vercally and the diaphragm is
operaonal.
E7.2
Flue fan current too low.
Check powerue cable is correctly plugged into the re and powerue.
Check powerue cable for damage.
E7.3
Flue fan current too high.
Check powerue fan is free spinning and not stalled or jammed.
Check powerue cable for damage.
E7.4
Pressure switch does not
close during purge.
Check whether the pressure switch is acvang at startup (there is an orange
indicator LED in the control tray and near the Aux buon).
Check that both ues are securely connected at both ends to the appliance and
the Power Flue wall terminal and that the ue is not damaged.
Check that the pressure switch electrical connecon is correct.
Check that the pressure switch hoses are connected at both ends. Ensure the
hoses are not kinked.
Ensure the pressure switch is mounted vercally and the diaphragm is
operaonal. The black hose should be connected to the lighter pressure port
and the translucent hose to the darker pressure port.
Check that the fan inside the Power Flue wall terminal is running during startup.
This fan may need servicing if it is slowed or stalled.