2. Commissioning
2−15
Festo P.BE−CPX−FB13−EN en 0811c
Mod.
no.
Module
Siemens order number
DP identifier
Siemens
DP identifier
EN 50170
Explanation
0 Field bus node
CPX−FB13:DP slave
[status]
64
d
40
h
, 00
h
Configured with status bits
1 Digital 8−input module
CPX−8DE [8DI]
8DI 10
h
Identifier byte used
completely
2 Digital 4−output module
CPX−4DA [4DO]x2
8DO 20
h
Only the first 4 bits of the
identifier byte are used
1)
MPA pneumatic interface
VMPA−FB−EPL−...
Passive module
3 MPA1 pneumatic module
MPA1S:
VMPA1−FB−EMS−8 [8DO]
8DO 20
h
MPA1 pneumatic modules
without separate power
supply circuits.
Identifier bytes are used
4 MPA1 pneumatic module
MPA1S:
VMPA1−FB−EMS−8 [8DO]
8DO 20
h
Identifier bytes are used
completely.
5 MPA2 pneumatic module
MPA2S: VMPA2−FB−
EMS−4 [4DO]x2
8DO 20
h
MPA2 pneumatic module
(without separate circuits)
Only the first 4 bits are used.
6 MPA2 pneumatic module
*MPA2S: VMPA2−FB−
EMS−4 [4DO]x0
0 00
h
MPA2 pneumatic module
(without separate circuits).
The remaining 4 bits of
module no. 5 are used.
1)
As no output module with groupable identifier is used in the subsequent locations,
8 bits are assigned here, but only 4 are used.
Tab.2/10: Configuration for example terminal 1
The identifier bytes of locations 5 and 6 are grouped together.
The identifier with the star symbol is used in location 6.