MS-9050 Series Manual — P/N 52413:F 10/22/2010 129
Master Programming Level Programming
3+1, 4+1 Express, and 4+1 Standard
The information shown in Table 3.3 is automatically programmed for the Central Station phone
number Event Codes when any of these Formats are selected. Enter 0 for an Event Code Setting to
disable the report.
Event Description
Event Code Settings
Active Restoral
PULL STATION 1 E
MON-USER-DEF-1 1 E
WATERFLOW 1 E
MON-USER-DEF-2 1 E
SMOKE (PHOTO) 1 E
DET-USER-DEF-1 1 E
SMOKE (ION) 1 E
DET-USER-DEF-2 1 E
HEAT DETECT 1 E
DET-USER-DEF-3 1 E
SMOKE DUCT-P 1 E
DET-USER-DEF-4 1 E
PHOTO W/HEAT 1 E
DET-USER-DEF-5 1 E
DUCT SUPERVISORY 8 E
DET-USER-DEF-6 8 E
PHOTO SUPERV 8 E
DET-USER-DEF-7 8 E
MONITOR 1 E
MON-USER-DEF-3 1 E
SMOKE CONVEN 1 E
MON-USER-DEF-5 1 E
HEAT CONVEN 1 E
MON-USER-DEF-6 1 E
MEDIC ALERT 0 0
MON-USER-DEF-7 0 0
HAZARD ALERT 0 0
MON-USER-DEF-8 0 0
TORNADO ALRT 0 0
MON-USER-DEF-9 0 0
TAMPER 8 E
MON-USER-DEF-11 8 E
MON SUPERVISORY 8 E
MON-USER-DEF-12 8 E
MON SUPERV AUTO 8 E
MON-USER-DEF-13 8 E
HVAC OVRRIDE 8 E
POWER MON 6 A
MON-USER-DEF-14 6 A
TROUBLE MON POINT_FAULT code will always be transmitted
MON-USER-DEF-15 POINT_FAULT code will always be transmitted
PROCESS MON 0 0
MON-USER-DEF-16 0 0
PROCMON AR 0 0
MON-USER-DEF-17 0 0
Table 3.3 Event Codes