MS-9050 Series Manual — P/N 52413:F 10/22/2010 133
Master Programming Level Programming
Ademco Contact ID Format
The information shown in Table 3.5 is automatically programmed for the Central Station phone
number Event Codes when Ademco Contact ID Format is selected. Enter 000 for an Event Code
Setting to disable the report.
Event Description
Event Code Settings
4+2
Active
Zone Point Restoral Active
PULL STATION 115 Zone Point E1 11
MON-USER-DEF-1 115 Zone Point E1 11
WATERFLOW 113 Zone Point E1 11
MON-USER-DEF-2 113 Zone Point E1 11
SMOKE (PHOTO) 111 Zone Point E1 11
DET-USER-DEF-1 111 Zone Point E1 11
SMOKE (ION) 111 Zone Point 11 11
DET-USER-DEF-2 111 Zone Point 11 11
HEAT DETECT 114 Zone Point 11 11
DET-USER-DEF-3 114 Zone Point 11 11
SMOKE DUCT-P 116 Zone Point 11 11
DET-USER-DEF-4 116 Zone Point 11 11
PHOTO W/HEAT 111 Zone Point 11 11
DET-USER-DEF-5 111 Zone Point 11 11
DUCT SUPERVISORY 200 Zone Point 11 81
DET-USER-DEF-6 200 Zone Point 11 11
PHOTO SUPERV 200 Zone Point 11 81
DET-USER-DEF-7 200 Zone Point 11 11
MONITOR 110 Zone Point 11 11
MON-USER-DEF-3 110 Zone Point 11 11
SMOKE CONVEN 111 Zone Point 81 11
MON-USER-DEF-5 111 Zone Point 11 11
HEAT CONVEN 114 Zone Point 81 11
MON-USER-DEF-6 114 Zone Point 11 11
MEDIC ALERT 100 Zone Point 11 0
MON-USER-DEF-7 100 Zone Point 11 0
HAZARD ALERT 150 Zone Point 11 0
MON-USER-DEF-8 150 Zone Point 11 0
TORNADO ALRT 150 Zone Point 11 0
MON-USER-DEF-9 150 Zone Point 11 0
TAMPER 144 Zone Point 0 81
MON-USER-DEF-11 144 Zone Point 0 81
MON SUPERVISORY 200 Zone Point 0 81
MON-USER-DEF-12 200 Zone Point 0 81
MON SUPERV AUTO 200 Zone Point 0 81
MON-USER-DEF-13 200 Zone Point 0 81
HVAC OVRRIDE 200 Zone Point 81 81
POWER MON 330 Zone Point 81 81
MON-USER-DEF-14 330 Zone Point 81 81
TROUBLE MON POINT_FAULT code will always be transmitted 81
MON-USER-DEF-15 POINT_FAULT code will always be transmitted 81
PROCESS MON 000 81 0
MON-USER-DEF-16 000 81 0
PROCMON AR 000 81 0
Table 3.5 Event Codes