Accutronix MX Maintenance & Spare Parts Manual 130-12000 Revision B • November 2002
5-26
Flow Control Division
Limitorque Actuation Systems
Electronic Assemblies
MX-85 & 140 only
Reconnect connectors 4 & 5 to motor lead harness.
STEP 6
Leave contactor assembly unmounted in control module
compartment to allow space for terminal block harness plug
bundle to be threaded over the top of the contactor
assembly and pulled into the control module cavity.
STEP 7
Reference Terminal Block Assembly procedures to remount
terminal block assembly into actuator. (See Section 5.4.2.)
Before mounting the contactor assembly, ensure the
terminal block wiring harness bundle is positioned across the
end of the contactor.
STEP 8
Position the contactor assembly so that the keyhole slots in
the contactor mounting plate allow the M4 screw heads to
pass through; shift the contactor assembly until the screw
heads seat in the key slots. Tighten screws using 3 mm hex
key to secure assembly.
STEP 9
8
6
7
Terminal block
wiring bundle
5a