Accutronix MX Maintenance & Spare Parts Manual 130-12000 Revision B • November 2002
5.2.2 Remounting
If the standard board set was separated from the DDC and/or I/O option boards, reassemble boards
back together as a complete unit before remounting the control module back into the actuator.
STEP 10
CAUTION
Ensure the voltage jumper on power board (see Figure 5.3) is located in the proper
slot for the nameplate and motor voltage!
a WARNING Hazardous Voltage! Turn off all power sources to actuator before remounting ACP
assembly. Power sources may include main power or control power.
CAUTION Potential to cause electrostatic damage to electronic components. Before handling
electronic components, ensure that you are discharged of static electricity by briefly touching a
grounded metal object.
Position control module subassembly over the three mounting screw heads (#8-7). Rotate the
subassembly in clockwise (CW) direction until all three screws are seated in the key slots. (The keyhole
slots in the mounting plate [#8-1] are spaced in such a way that the control module assembly will
mount in only one position).
STEP 11
Tighten the three screws (#8-7) with a 3 mm hex key.
STEP 12
NOTE: Ensure wiring harness bundle routes through the semicircular
slots on the printed circuit boards.
Connect the 6-pin Molex
®
wire harness to plug P1 and
14-pin Molex
®
harness to plug P2 on main power board.
5-8
Flow Control Division
Limitorque Actuation Systems
Electronic Assemblies
10
11
12
8-7
P2
P1
a
a