Electronic Assemblies
Accutronix MX Maintenance & Spare Parts Manual 130-12000 Revision B • November 2002
STEP 2
Lift contactor assembly until the keyhole slots in the
contactor mounting plate allow the heads of the M4
screws to pass through.
STEP 3
Remove the contactor assembly while threading the motor
power socket out of the motor compartment.
NOTE: Only the MX-05, 10, 20 & 40 have the long motor
power socket lead.
MX-85 & 140
Disconnect connectors 4 & 5 to motor lead harness.
5.5.2 Remounting
STEP 4
Insert contactor assembly into control module cavity.
STEP 5
(MX-05, 10, 20, 40, 85 & 140)
Route leads L1, L2, and L3 (input power) to the terminal
block cavity.
MX-05, 10, 20 & 40 only
Feed the motor power plug through the housing to the
motor cavity.
5-25
Flow Control Division
Limitorque Actuation Systems
4
5
Motor power plug
Motor Cavity
Terminal block
cavity
2
3
Motor power
plug