Accutronix MX Maintenance & Spare Parts Manual 130-12000 Revision B • November 2002
STEP 5
Hold the motor assembly (housing/stator/rotor) close to the actuator
housing and reconnect the motor power plug to the motor power
socket connector.
STEP 6
Coil the spiral-wrapped motor power wiring inside the motor cavity
and around the motor bearing housing to ensure that it does not
come into contact with the rotor shaft.
MX-05 through 40 motor wiring will wrap around about 360˚. MX-
85/140 motor wiring will wrap around about 180˚.
STEP 7
Push the rotor shaft onto the protruding worm shaft, aligning the
rotor shaft slots with the worm shaft pin. Slide the motor housing
spigot/pilot into the actuator housing.
STEP 8
Fit the four screws (#1-14) into the motor subassembly mounting
holes and tighten.
4-3
Flow Control Division
Limitorque Actuation Systems
Mechanical Assemblies
5
7
8
Motor Power
Socket
Connector
Motor Power
Plug
1-14
6