EasyManua.ls Logo

Flowserve MASTER STATION IV EEP-SN4001 - Figure 7.17 - Configure DCS Ethernet Port; Figure 7.18 - Configure DCS Data Table Menu

Flowserve MASTER STATION IV EEP-SN4001
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Limitorque
®
Master StationI V EEP-SN4001 FCD LMENIM5010-00-AQ – 03/19
37
flowserve.com
7.2.5.2 Ethernet Port
The Ethernet port assigned to the control system’s Host device is configured via the Configure Ethernet Port menu to
communicate via Modbus TCP/IP. Set the desired IP address, subnet mask, and gateway, then Accept and save the
settings. Note that if 2 redundant modules are used, each module must be configured with a unique IP address. Note:
use port 502 for Modbus TCP/IP communications.
Figure 7.17 – Configure DCS Ethernet Port
7.2.5.3 Configure Data Table
The MSIV data table is configurable for the Modbus Function codes 02, 03, 05/15, and 06/16. The Modbus function
code 01 has a fixed data table and does not permit user alteration. The data tables are edited by using the Configure Data
Table menu shown below.
Figure 7.18 – Configure DCS Data Table Menu

Table of Contents

Related product manuals