EasyManua.ls Logo

Fluid Components Intl ST51A - Checking K Factor Values; Changing;Setting K Factor Values

Fluid Components Intl ST51A
114 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATION ST51A/ST75A/ST75AV Mass Flow Meters
62 Fluid Components International LLC
Checking K Factor Values
Referring to Checking the Totalizer Value
above, repeat step 1, but specify register
#41xx instead (i.e., K Factor registers
#4107 through #4114). In this case, specify
Length as “2” to check an MS/LS pair (i.e.,
4107, 4109, 4111, or 4113). Or specify
register #4107 with Length = “8” to check
them all (4 pairs) at once. Assuming that
ModScan32 is already connected and
configured, the K Factor registers are then
displayed as shown at right after clicking
OK in the Data Definition dialog (with
Length = “8”).
Changing/Setting K Factor Values
In the below example, the desired value of K Factor 1 is 2.4 (floating point). This floating point number is converted into a hexadecimal
value (0x4019999A), which is then programmed into Modbus registers #4107 (Most Significant) and #4108 (Least Significant).
1. Referring to Changing/Setting K Factor Values above, use the Display Definition dialog to show all K Factor registers (i.e., specify
register #4107 with Length = “8”.
2. Double click on the MS register #4107 line
(see figure at right). In the resulting Write
Register dialog, enter “4019” in the
window’s value field, and then click
Update.
DOUBLE CLICK
ENTER VALUE

Table of Contents

Related product manuals