21-1
Chapter 21
Logger
Introduction
Logger is a function that gives you the possibility to log multiple readings with high
resolution. The readings are observed during adjustable time intervals. At the end of the
interval the min, max, and average values of all readings are stored and the next
observation interval starts. This process continues for the Duration of the observation
period.
The Analyzer has as a default a predefined set of readings that is used for logging. This
set can be customized to your own set of readings. Via the Setup Readings from the
logger start menu you can Add or Remove readings to be logged.
You start the Logging function from the Start menu that allows you to select the Interval
time (0.25 s – 2 Hr.), the readings to be logged, the maximum duration of the logging
(1 Hr. – Max) and Immediate or Timed start of logging.
Readings are displayed in a Meter screen, a Trend screen, and an Events Table.
Start Menu
To access the Logger Start Menu:
c
LOGGER
The set of readings to be logged is selectable in the menu under function key F1 –
SETUP READINGS. The reading selection list for default frequency 50/60 Hz and
400 Hz are different. If you change the default frequency to 400 Hz or from 400 Hz to
50/60 Hz the reading selection list will be set to default!
With the up/down arrow keys you can select the Category of readings to be logged. These
Categories are listed in Column 1: Volt, Amp, Power, Energy, Volt Harmonic, Amp
Harmonic, Watt Harmonic, Frequency, Flicker (not for 400 Hz), Unbalance, and Mains
Signaling (not for 400 Hz).