Monitor is intended to perform a quality check over a long period up to one week. For
compliance to international standards averaging time for Vrms and Harmonics are 10
minutes. This allows you to obtain a good impression of power quality, but is less
suitable for troubleshooting. For troubleshooting the measuring functions like Dips and
Swells or Logger are more suitable.