Safety In order to connect optional components, it may be necessary to open the hous-
ing. The following warning notices must be obeyed:
WARNING!
Danger from electric shocks.
This can result in serious injury or death.
The housing must never be opened by anyone other than a service technician
trained by the manufacturer.
The device must be disconnected from the grid before starting any work with
the housing open.
A suitable measuring instrument must be used to ensure that electrically
charged components (e.g. capacitors) are fully discharged.
Use an easily legible and understandable warning sign to ensure that the
device is not reconnected to the grid before all the work has been com-
pleted.
WARNING!
Danger due to work that has been carried out improperly.
This can result in serious injury and damage to property.
All work involved with connecting optional components must only be carried
out by qualified specialist technicians.
If Installation Instructions or User Information is available for the optional
component concerned, all warning notices and instructions therein must be
obeyed.
In the case of all optional components with electrical connections, once the
connection work is complete, a safety inspection must be carried out in ac-
cordance with relevant national and international standards and directives.
Further details on safety inspections can be obtained from your authorised
service centre.
They will provide you with any documents you may require on request.
WARNING!
Danger from devices falling or toppling over.
This can result in serious injury and damage to property.
Due to its weight, the device must be secured using suitable fittings to pre-
vent it from toppling or falling over.
The wall and floor brackets provided by the manufacturer must be used.
Electrolyte cir-
culation (not
available on the
Selectiva 3x220
16 kW variants)
NOTE!
Danger due to the ingress of electrolyte from the battery or due to operation
without any back pressure.
This may result in damage to the air pump.
Always set up the charger at least 0.5 m (1 ft. 7.69 in.) above the battery to
be charged.
Always use an undamaged connecting hose provided specifically for this pur-
pose to connect the charger's compressed air outlet to the battery.
56

Table of Contents

Other manuals for Fronius Selectiva 3.0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Selectiva 3.0 and is the answer not in the manual?

Fronius Selectiva 3.0 Specifications

General IconGeneral
BrandFronius
ModelSelectiva 3.0
CategoryBattery Charger
LanguageEnglish

Related product manuals