Country-specific set-
ting:
Setup
Specified country setup
Version
Version of country setup
Alternative (emergency power) or original country setup activ-
ated
Group
Group for updating the inverter software
MPP Tracker: PV Tracker
Grid monitoring: GMTi
Start-up time of inverter in s
GMTr
reconnection time in s following a grid fault
ULL
Mean grid voltage over 10 minutes in V
LLTrip
Trip time for long-term voltage monitoring
Grid voltage limits: UILmax
Upper inner grid voltage in V
UILmin
Lower inner grid voltage in V
Grid frequency limits: FILmax
Upper inner grid frequency in Hz
FILmin
Lower inner grid frequency in Hz
Q-mode: Current cos phi power factor setting
(e.g. Constant Cos(phi) / Constant Q / Q(U) characteristic /
etc.)
AC power limit: Max. P AC
Manual power reduction
AC voltage derating: Status
ON / OFF – Voltage-dependent power reduction
GVDPRe
Threshold at which the voltage-dependent power reduction
begins
GVDPRv
Reduction gradient used to reduce the power, e.g.: 10% per
volt above the GVDPRe threshold
Message
Activates the sending of an info message via Fronius Solar
Net
61