EasyManua.ls Logo

Fronius Symo Hybrid 3.0-3-S - System Monitoring Unit: Controls and Indicators; Unit Controls, Indicators, and Network Settings

Fronius Symo Hybrid 3.0-3-S
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- Dedicated web page displaying current data and a wide range of settings
- Option of connecting directly to Fronius Solar.web
- Internet connection via WLAN or LAN
- Ability to control the inverter load by specifying power limit values, minimum or max-
imum running times or target running times
- Ability to control the inverter via Modbus (TCP)
- Ability to assign control priorities
- Ability to control the inverter by means of connected meters (Fronius Smart Meter)
- Ability to control the inverter via a ripple control signal receiver (e.g. by specifying
the reactive power or effective power)
- Dynamic power reduction, taking self-consumption into account
- Ability to control battery charging in line with the control targets set
- Ability to control emergency power mode
Controls, connec-
tions and indicat-
ors on the sys-
tem monitoring
unit
(5)
(1)
(6)(7)(8)(9)
(4)
(2)
(3)
LAN
No
.
Function
(1) IP switch
For switching the IP address:
Switch position A
Default IP address with activating of the WLAN access point
Setting the IP switch to position A also opens an access point to enable a
direct WLAN connection to system monitoring.
Access data for this access point:
Network name: FRONIUS_239.XXXXXX
Key: 12345678
System monitoring can be accessed by:
- Using the DNS name "http://datamanager"
- Using the IP address 169.254.0.180 for the LAN interface
- Using the IP address 192.168.250.181 for the WLAN access point
38

Table of Contents