Fault Ride Through: Status – Default setting: OFF
If the function is activated, the inverter does not switch off
immediately in the event of a short-term AC voltage dip (out-
side of the limits specified by the grid supplier), but instead
continues to feed in power for a defined period.
DB min – Default setting: 90%
"Dead Band Minimum" setting in per cent
DB max - Default setting: 120%
"Dead Band Maximum" setting in per cent
k-Fac. - Default setting: 0
Version Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)
Display area Display / Display Software / Integrity Checksum / Memory
Card / Memory Card #1 / Power Stage / Power Stage Soft-
ware / EMI Filter / Power Stage #3 / Power Stage #4