INF-TN1FSC-E 169
Detector (Type: FLD)
Type of detector:
Kind Type Internal pipe diameter (mm) Fluid temperature
Small type FLD12
φ50 to φ400
−40 to 100°C
Small diameter FLD22
φ13 to φ100
−40 to 100°C
High temperature FLD32
φ50 to φ400
−40 to 200°C
Middle type FLD41
φ200 to φ1200
−40 to 80°C
Large type FLD51
φ200 to φ6000
−40 to 80°C
Mounting method: Mounting on outside of existing pipe
Sensor mounting method: V or Z method
Signal cable: Exclusive coaxial cable
Standard 5m
Method for connection: Flow transmitter side
Exclusive connector
Detector side
Large/middle type: Screw terminal
Others: BNC connector
Ambient temperature: −20 to +60°C
Ambient humidity: Large/middle type sensor: 100%RH or less
Others: 90%RH or less
Type of enclosure: Large/middle type sensor: IP67
Others: IP52
Material and mounting belt/wire:
Kind Type Sensor case Mounting bracket Mounting belt /wire
Small diameter FLD22 Plastic Aluminum alloy + Plastic Plastic cloth belt
Small type FLD12 Plastic Aluminum alloy + Plastic Plastic cloth belt
Middle type FLD41 Plastic −− Stainless wire
Large type FLD51 Plastic −− Stainless wire
High temperature FLD32 SUS304 Aluminum alloy + SUS304 Stainless belt
Extension cable (option): Extended when the length of the detector signal cable is not suffi cient.
Length: 10m, 50m
FLOW VELOCITY PROFILE DISPLAY FUNCTION (OPTION)
Flow velocity profi le can be observed in real time using the dedicated detector from the outside. It is specifi able by the
code symbol of fl ow transmitter.
APPLICATION
Pulse Doppler method is applicable to observe fl ow velocity profi le in real time, display the fl ow status in the pipe, and
decide the appropriate measurement location. Also, it can be used for diagnosis of fl ow and laboratory test.
SPECIFICATIONS
Measuring fl uid: Uniform liquid in which ultrasonic waves can propagate.
Turbidity of fl uid: Axisymmetric fl ow in a fi lled pipe.
Fluid temperature: −40 to +100°C (FSDP2)
−40 to +80°C (FSDP1,FSDP1)
Air bubble quantity: 0.02 to 15Vol% (Velocity is 1m/s)
Pipe size: Small type sensor : φ40 to φ200mm
Middle type sensor :φ100 to φ400mm
Large type sensor :φ200 to φ1000mm
Measurement range: 0 to ±0.3: ±Maximum Velocity (depending on the pipe diameter) Refer to chart, page 139.
Note) This function is to observe fl ow velocity profi le, and it may be different from actual
fl ow rate.