Table
2-13
怀怀
Electrical
specifications
(Expansion
rack:
Single-phase
power
feed
model)
(*1)
(continued)
Item Specification
1
expansion
rack 2
expansion
racks
Input
voltage 200
to
240
VAC 200
to
240
VAC
Leakage
current
(*3)
(*4) 3.5
mA 3.5
mA
*1
The
specifications
apply
to
a
single
rack.
*2
For
the
M10-4S
mounted
in
an
expansion
rack.
If
the
mounted
device
is
not
the
M10-4S,
the
configuration
may
be
different
depending
on
the
power
connection
configuration
of
the
device.
*3
The
value
is
the
tolerance
per
power
cord.
The
actual
current
value
depends
on
the
rating
of
the
device
mounted
in
the
expansion
rack.
*4
The
value
is
for
an
expansion
rack
without
the
M10-4S
and
other
devices
mounted.
(Only
crossbar
boxes
are
mounted.)
Only
the
two
power
cords
use
power.
If
the
M10-4S
or
other
devices
are
mounted,
the
current
values
and
the
number
of
power
cords
that
consume
power
are
different.
*5
The
current
that
flows
through
each
power
cord
in
a
redundant
configuration
is
half
the
value
listed
in
Table
2-13.
Table
2-14
怀怀
Electrical
specifications
(Expansion
rack:
Three-phase
delta
power
feed
model)
(*1)
Item Specification
1
expansion
rack 2
expansion
racks
Input
voltage 200
to
240
VAC 200
to
240
VAC
Number
of
power
cords 6 6
Power
cord
length 4.0
m
(13.1
ft.) 4.0
m
(13.1
ft.)
Redundancy
(*2) 1+1
redundant
configuration 1+1
redundant
configuration
Frequency 50
Hz/60
Hz 50
Hz/60
Hz
Rated
current
(*3) Maximum
of
35
AMaximum
of
35
A
Rated
current
(*4)
(*5) 4.0
A5.2
A
Maximum
power
consumption
(*4) 1,354
W1,754
W
Apparent
power
(*4) 1,382
VA 1,790
VA
Rush
current
(*3)
(*4) 80
A
peak
or
less 80
A
peak
or
less
Leakage
current
(*3)
(*4) 3.5
mA 3.5
mA
*1
The
specifications
apply
to
a
single
rack.
*2
For
the
M10-4S
mounted
in
an
expansion
rack.
If
the
mounted
device
is
not
the
M10-4S,
the
configuration
may
be
different
depending
on
the
power
connection
configuration
of
the
device.
*3
The
value
is
the
tolerance
per
power
cord.
The
actual
current
value
depends
on
the
rating
of
the
device
mounted
in
the
expansion
rack.
*4
The
value
is
for
an
expansion
rack
without
the
M10-4S
and
other
devices
mounted.
(Only
crossbar
boxes
are
mounted.)
Only
the
two
power
cords
use
power.
If
the
M10-4S
or
other
devices
are
mounted,
the
current
values
and
the
number
of
power
cords
that
consume
power
are
different.
*5
The
current
that
flows
through
each
power
cord
in
a
redundant
configuration
is
half
the
value
listed
in
Table
2-14.
Table
2-15
怀怀
Electrical
specifications
(Expansion
rack:
Three-phase
star
power
feed
model)
(*1)
Item Specification
1
expansion
rack 2
expansion
racks
Input
voltage 380
to
415
VAC 380
to
415
VAC
Number
of
power
cords 6 6
Power
cord
length 4.0
m
(13.1
ft.) 4.0
m
(13.1
ft.)
Chapter
2
怀
Planning
and
Preparing
for
System
Installation 57

Table of Contents