36 Operating manual RX300 S3
Installing/Removing the Server into/from the Rack Hardware Installation
3rd-Party Rack
Certain boundary conditions are to be fulfilled:
– Installation dimensions (see the dimensions shown in figure 4 on page 37).
– The operability of the safety mechanisms at the server e.g. stoppers or
holding back systems must be guaranteed.
– The form of the rack support uprights must ensure the frontal screwing on of
the rails.
– Frontally bolted telescopic rails.
The rails are provided with a linear alignment possibility to ensure also an
adjustment to different rack depths.
– No support of the cable management (delivered with the mounting kit).
– Climatic conditions.
For the ventilation of the installed server a large extent unhindered air intake
in the rack front and air discharge in the rear cover of the rack are necessary.
1 rack front side
2 rack rear side
A rack depth (comparison PRIMECENTER Rack 940/1000 mm)
B rack width (comparison PRIMECENTER Rack 700 mm)
C clearance of the 19-inch installation level
C1 front 19-inch installation level
C2 rear 19-inch installation level
D area for cable routing (cable area depth) and ventilation
E area for front panel and ventilation
F right and left area for support systems
P PRIMERGY installation depth
a1 front left support upright
a2 front right support upright
b1 rear left support upright
b2 rear right support upright