11-8 VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003 GFK-1504K
11
IC200ALG320
Analog Output Module, 12 Bit Current, 4 Channels
Thermal Derating
The minimum recommended load resistance per channel depends on the ambient
temperature, the external voltage, and the orientation of the module and DIN rail. The
thermal derating is not affected by the type of carrier on which the module is installed.
The total load requirement includes the impedance of the transducer being driven. At
higher ambient temperatures, it may be necessary to add resistance in series with the load
to reach the minimum load requirement.
A A
B
A
B
B
Ambient Tem
p
erature
Minimum Load Resistance
p
er Channel
(
Ohms
)
60ºC50ºC 55ºC45ºC40ºC35ºC
30ºC
25ºC20ºC15ºC10ºC
5ºC
1000
750
500
250
875
625
375
125
B
A
24VDC
B
A
24VDC
30VDC
30VDC