ADV200 SP • Quick start up guide - Specification and installation 53
Step 2 - Setting motor parameter (Set motor data)
Set the rating data of the motor connected: rated voltage, rated frequency, rated current, rated speed, rated
10 Hp
Motor: 3 phase
720 rpm
Motor &Co.
Type: ABCDE
380 V
IP54
Made in ..............
19.0 A
IEC 34-1/VDE 0530
Iso Kl F
Nr
.
12345-91
S1
50 Hz
Power factor
0.83
I nom
Rated voltage
Rated power
Rated speed (n )
N
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
T+ T- EN LO C ILim n:0 AL
STARTUP WIZARD
Set motor data ?
E=Yes Down=Next
E
T+ T- EN LO C ILim n:0 AL
SEQ.01
PA R: 2000
Rated voltage
+400 V
Def: +400
T+ T- EN LO C ILim n:0 AL
13.01
PA R: 100
Rated voltage
+ V
Def: +400
000000400
E
T+ T- EN LO C ILim n:0 AL
SEQ.01
PA R: 2000
Rated voltage
+ V
Def: +400
000000400
T+ T- EN LO C ILim n:0 AL
SEQ.01
PA R: 2000
Rated voltage
+ V
Def: +400
000000380
E
E
T+ T- EN LO C ILim n:0 AL
SEQ.02
PA R: 2002
Rated current
+11.8 A
Def: +11.8
E E
T+ T- EN LO C ILim n:0 AL
SEQ.02
PA R: 2002
Rated current
+ 0000011.8 A
Def: +11.8
E
T+ T- EN LO C ILim n:0 AL
SEQ.02
PA R: 2002
Rated current
+ A
Def: +11.8
0000019.0
T+ T- EN LO C ILim n:0 AL
SEQ.03
PA R: 2004
Rated speed
+1450 rpm
Def: +1450
E E
E
T+ T- EN LO C ILim n:0 AL
SEQ.03
PA R: 2004
Rated speed
+ rpm
Def: +1450
000000720
T+ T- EN LO C ILim n:0 AL
SEQ.03
PA R: 2004
Rated speed
+ 000001450 rpm
Def: +1450
T+ T- EN LO C ILim n:0 AL
SEQ.04
PA R: 2006
Rated frequency
+
50.0
Hz
Def: +50.0
T+ T- EN LO C ILim n:0 AL
SEQ.05
PA R: 2008
Pole pairs
+2
Def: +2
E E
E
T+ T- EN LO C ILim n:0 AL
SEQ.05
PA R: 2008
Pole pairs
+
Def: +2
000000004
T+ T- EN LO C ILim n:0 AL
SEQ.05
PA R: 2008
Pole pairs
+ 000000002
Def: +2
T+ T- EN LO C ILim n:0 AL
SEQ.06
PA R: 2010
Rated power
+5.50 kW
Def: +5.50
E E
E
T+ T- EN LO C ILim n:0 AL
SEQ.06
PA R: 2010
Rated power
+ kW
Def: +5.50
000007.36
T+ T- EN LO C ILim n:0 AL
SEQ.06
PA R: 2010
Rated power
+ 000005.50 kW
Def: +5.50
T+ T- EN LO C ILim n:0 AL
SEQ.07
PA R: 2012
Rated power factor
+0.83
Rated Voltage [V]: motor rated voltage as indicated on the data plate.
Rated current [A]:
current of the drive, output current class 1 @ 400V on the rating plate of the drive.
Rated speed [rpm]:
frequency. If slip is indicated on the motor rating data, set the Rated speed parameter
as follows:
Rated speed = Synchronous speed - Slip
Rated frequency [Hz]: motor rated frequency, as shown on the data plate.
Pole pairs:
on the plate and the following formula: P = 60 [s] x f [Hz] / nN [rpm]
Where: p = motor pole pairs
f = motor rated frequency (menu 16 MOTOR DATA par. 2006)
nN = motor rated speed (menu 16 MOTOR DATA par. 2004)
Rated power [kW]: motor rated power, for a motor rating plate with a HP power value, set the rated power
kW = 0.736 x motor power Hp value.
Rated power factor:
Note ! When data entry is complete the Take parameters command (menu 16 MOTOR DATA, PAR: 2020) is executed auto-
matically. The motor data entered during the STARTUP WIZARD procedure are saved in a RAM memory to enable the
drive to perform the necessary calculations.
These data are lost if the device is switched off. To save the motor data follow the procedure described in Step 6.