Note: Before to set up 00-32 Application, it should do initialized setting (parameter 13-08) first. When setting 00-32, the I/O
port function changed automatically. To avoid accident, be sure to confirm the I/O port signal of inverter and external
terminal control
00-32=2: Conveyor
Parameter Name Value
00-00 Control mode selection 0: V/f
00-14 Acceleration time 1 3.0 sec
00-15 Deceleration time 1 3.0 sec
00-27 HD/ND selection 0: HD
08-00 Stall prevention function xx0xb: Stall prevention during deceleration
00-32=3: Exhaust fan
Parameter Name Value
00-00 Control mode selection 0: V/f
11-00 Direction lock selection 1: Forward direction only
00-27 HD/ND selection 1: ND
01-00 V/f curve selection F
07-00 Momentary stop and restart selection 1: Enable
08-00 Stall prevention function xx0xb: Stall prevention during deceleration
00-32=5: Compressor
Parameter Name Value
00-00 Control mode selection 0: V/f
11-00 Direction lock selection 1: Forward direction only
00-14 Acceleration time 1 5.0 sec
00-15 Deceleration time 1 5.0 sec
00-27 HD/ND selection 0: HD
01-00 V/f curve selection F
07-00 Momentary stop and restart selection 1: Enable
08-00 Stall prevention function xx0xb: Stall prevention during deceleration
00-32=6:Hoist*ConsultGefranforthedetailedsettings
Parameter Name Value
00-00 Control mode selection 2: SLV
00-05 Main Frequency command source selection 0: keypad
11-43 Hold Frequency at start 3.0 Hz
11-44 Frequency hold Time at start 0.3 sec
00-14 Acceleration time 1 3.0 sec
00-15 Deceleration time 1 3.0 sec
11-01 Carrier frequency 5.0kHz
05-01 Frequency setting of speed-stage 0 6.0 Hz
05-02 Frequency setting of speed-stage 1 30.0 Hz
05-03 Frequency setting of speed-stage 2
50.0 Hz
03-28 Photo-coupler output 5 : frequency detection 2
07-18 Minimum baseblock time 0.3 sec
08-00 Stall prevention function
0000b: Stall prevention ineffective in decel-
eration
03-13 Frequency detection level 2.0 Hz
03-14 Frequency detection width 0.1 Hz
08-18 Selection of low-torque operation 0: Deceleration to stop
08-19 Level of low-torque detection 2 %
08-20 Time of low-torque detection 0.5 sec
08-09 Selection of input phase loss protection 1 : Enable
08-10 Selection of output phase loss protection 1 : Enable
00-32=7:Crane*ConsultGefranforthedetailedsettings
Parameter Name Value
00-00 Control mode selection 0: V/f
00-05 Main Frequency Command Source Selection 0: keypad
00-14 Acceleration time 1 3.0 sec
00-15 Deceleration time 1 3.0 sec
VDI100 • Instruction manual 107