13-08=8: PLC initialization
Clear built-in PLC ladder logic and related values.
13-08=9: 2 wire Initialization (60Hz) (230/460V)
The same as 18-08=2
13-08=10: 3 wire Initialization (60Hz) (230/460V)
The same as 18-08=3
13-08=11: 2 wire Initialization (60Hz) (230/400V)
The same as 18-08=2, Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V
class).
13-08=12: 3 wire Initialization (60Hz) (230/400V)
The same as 18-08=3, Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V
class).
13-08=13: 2 wire Initialization (50Hz) (230/400V)
The same as 18-08=2, Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V
class).
13-08=14: 3 wire Initialization (50Hz) (230/400V)
The same as 18-08=3, Inverter input voltage (01-14) is automatically set to 230V (200V class) or 440V (400V
class).
Parameters don’t be inuenced by Restore factory setting / Initialize (13-08):
No. parameters
00-00 Control Mode Selection
00-04 Language
00-27 HD/ND Mode Selection ***
01-00 V/f Curve Selection
01-26 V/f Curve Selection of Motor 2
13-00
Inverter Model Selection
13-03 Cumulative Operation Hours 1
13-04 Cumulative Operation Hours 2
13-05 Selection of Cumulative Operation Time
Code Parameter Name / Range
13-09 Fault history clearance function
0: Do not clear fault history
1: Clear fault history
13-09=1: Clears inverter fault history.
Note: parameters 12-11~12-15/12-45~12-64 are cleared as well.
Code Parameter Name / Range
13-10 Parameter Password Function 2
0 ~ 9999
13-11 C/B CPLD Ver.
0.00~9.99
This parameter displays the CPLD software version on the control board. It is only displayed on the control
board with CPLD.
244 VDI100 • Instruction manual