Group 10: PID Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/f
V/f
+PG
SLV SV
PM
SV
PM
SLV
SLV2
10-36
~
10-38
Reserved
10-39
*Output Frequency Setting
of PID Disconnection
00.00~599.00 30.00 Hz O O O O O O O
10-40
Selection of PID Sleep Com-
pensation Frequency
0: Disable
0 O O O O O O O
1: Enable
* If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz
Group 11: Auxiliary Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/f
V/f
+PG
SLV SV
PM
SV
PM
SLV
SLV2
11-00 Direction Lock Selection 0: Allow Forward and Reverse Rotation 0 - O O O O O O O
1: Only Allow Forward Rotation
2: Only Allow Reverse Rotation
11-01 Carrier frequency 0: Carrier Output Frequency Tuning * - O O O O O O O
1: 1KHz
2~16: 2~16kHz
11-02
Soft PWM Function
Selection
0: Disable 0 - O O O O O O O
1: Enable
11-03
Automatic carrier lowering
selection
0: Disable 0 - O O X X X X O
1: Enable
11-04
S-curve Time Setting at the
Start of Acceleration
0.00~2.50 0.20 s O O O O O O O
11-05
S-curve Time Setting at the
Stop of Acceleration
0.00~2.50 0.20 s O O O O O O O
11-06
S-curve Time Setting at the
Start of Deceleration
0.00~2.50 0.20 s O O O O O O O
11-07
S-curve Time Setting at the
Stop of Deceleration
0.00~2.50 0.20 s O O O O O O O
11-08 Jump Frequency 1 0.0~599.0 0.0 Hz O O O O O O O
11-09 Jump Frequency 2 0.0~599.0 0.0 Hz O O O O O O O
11-10 Jump Frequency 3 0.0~599.0 0.0 Hz O O O O O O O
11-11 Jump Frequency Width 0.0~25.5 1.0 Hz O O O O O O O
11-12 Manual Energy Saving Gain 0~100 80 % O O X X X X X
11-13 Automatic Return Time 0~120 60 s O O O O O O O *1
11-14
~
11-17
Reserved
11-18
Manual Energy Saving
Frequency
0.0~599.0 0.00 Hz O O X X X X X
11-19
Automatic Energy Saving
Function
0: Automatic energy saving is disabled. 0 - O X X X X X X
1: Automatic energy saving is enabled.
11-20
Filter Time of Automatic
Energy Saving
0~200 140 ms O X X X X X X
11-21
Voltage Upper Limit of
Energy Saving Tuning
0~100 100 % O X X X X X X
11-22
Adjustment Time of Auto-
matic Energy Saving
0~5000 20 ms O X X X X X X *1
11-23
Detection Level of Automa-
tic Energy Saving
0~100 10 % O X X X X X X
11-24
Coefficient of Automatic
Energy Saving
0.00~655.35
S - O X X X X X X
11-25
~
11-27
Reserved
76 VDI100 • Instruction manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran VDI100 Series and is the answer not in the manual?

gefran VDI100 Series Specifications

General IconGeneral
Brandgefran
ModelVDI100 Series
CategoryInverter
LanguageEnglish

Related product manuals