Why am I getting a UV Under voltage error on my gefran VDI100 Inverter?
- LlisagomezAug 29, 2025
If your Gefran Inverter is showing a UV (Under Voltage) error, it could be due to several reasons. The input voltage might be too low, so check the input voltage. There might be an input phase loss, so check the input wiring. The acceleration time might be set too short, so increase the acceleration time. Input voltage fluctuation could also be the cause, so check the power source. The pre-charge contactor could be damaged, so replace the pre-charge contactor. Also, the DC bus voltage feedback signal value might be incorrect, so replace the control board or the entire inverter.