30
Instruction manual
Electric Actuators Type EA15-250
6.2 Adjusting end positions
The two end positions in the actuator have been factory set to 90°. A readjustment may be required after assembly by the customer
or after repair work.
The end positions can be set via the 4 buttons on the base board.
4 buttons
SET STORE CCW CW
Buttons
1. Open cover. To do so, loosen the 4 screws (torx size 20).
2. Connect the actuator to the appropriate power and let it rotate, until an end position is reached.
NOTE!
If an end position is not reached, the actuator automatically switches o after 2 min. and displays a fault message.
Adjusting end positions
Step Press button Position indicator
Repeat for every position
1.
SET* >3 s Blue flashing
2.
SET* Until color Blue/Red=OPEN Bau
Blue/Green=CLOSED
Blue/White=MIDDLE*
3.
CW
CCW
Until end position
CW
CCW
4.
STORE Briefly Position color
5.
Check position indicator color
6.
Next position press SET within 10 sec.
*EA25-250
3. Repeat this process, until all positions are adjusted.
4. Reinstall the cover and fasten it with the 4 screws.