7.2 Assignment of error codes
In case of a fault, the error codes will be displayed on the 7 segment display on the base board.
Error code Description “Ready-to-opera-
te” signal
EA response
---- No voltage No None
U Voltage below specification No None
O Housing internal temperature too high (>80 °C) No Stops
S Time from end position to end position too long (> 120s) No Stops
b Voltage above specification No Stops
h Heating defective and T = < 0 °C No Normal operation
e Error in position detection No None
P Invalid position No Normal operation
E Emergency manual override active No None
9 No communication with accessories No None
I Actuator was run in motor current limit No Stops
Further error codes can be found in the corresponding accessory user manuals.