32
2.3 Automatic closing
With this menu item, you can select a time between 1 and 240
seconds after which the door closes automatically.
For this purpose, you must activate an operation mode (menu
item
0.1) with the option self-hold OPEN/CLOSE.
You can connect a switch for activating and deactivating this
function to terminals X4.1 and X4.2. The programmed time
remains stored.
2.3
Setting of automatic closing
►
.0
Deactivated
. 1 - 2.40
Activated.
. 1 = 1 second up to 9.9 = 99 seconds
Formorethan99seconds,thedisplaywillashtwicetoshow3-digit
numbers in full:
1.- and 0.0 = 100 seconds up to 1.- and 9.9 = 199 seconds
2.- and 0.0 = 200 seconds up to 2.- and 40 = 240 seconds
You can interrupt automatic closing manually:
▪ PresstheSTOPbuttonwhenthedoorisinnallimitposition
OPEN. The door remains open.
▪ Press the OPEN button to reactivate automatic closing timer.
With menu item
2.4 you can set whether activation of a
photocell interrupts automatic closing.