EasyManua.ls Logo

GFA DC 8010 - 5.4 Motor cable conductor size

GFA DC 8010
55 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
5.4 Motor cable conductor size
Drives with AC motor
Drives
Mains Voltage Control
Unit
Fuse
Ambient Temperature
Correction Factor to
30°C / 86°F
[Based on Temperature
Rating of Conductor
75°C / 167°F]
(NFPA 70 Table 400.5(A))
Ambient Temperature
Correction Factor to
40°C / 104°F
[Based on Temperature
Rating of Conductor
75°C / 167°F]
(NFPA 70 Table 400.5(A))
all
drives
3~220 V
3~460 V
3~575 V
< 10,5 A 15 A 14 AWG 14 AWG
Drives with VFD motor
VFD Motor
Mains
voltage
input
current
Control Unit Fuse Ambient
Temperature
Correction Factor to
30°C / 86°F
[Based on
Temperature Rating
of Conductor
75°C / 167°F]
(NFPA 70 Table
400.5(A))
Ambient
Temperature
Correction Factor
to 40°C / 104°F
[Based on
Temperature Rating
of Conductor
75°C / 167°F]
(NFPA 70 Table
400.5(A))
0,85 kW
D7FG4uS/
FU085UL
2 ~ 220 V
7,0 A
15 A 14 AWG 14 AWG
1,5 kW
D9LHu4(S)/
FU150UL
2 ~ 220 V
12,0 A
15 A 14 AWG 12 AWG
4,5 kW
D9LLM4u(S)/
FU450UL
3 ~ 460 V
12,0 A
15 A 14 AWG 12 AWG
4,5 kW
D9LLM4u(S)/
FU450LVUL
3 ~ 240 V
16,3 A
20 A 12 AWG 10 AWG

Table of Contents