secondary current of the external CT.
Built in electric meter or GMK110: No need to set CT
ratio. The default CT ratio is 120A/40mA.
GM330: Supports purchasing from GOODWE or
third-party, CT ratio requirement: nA/5A
nA: For the primary input current of CT, n ranges
from 200 to 5000.
5ASecondary output current of CT.
9.4.4 Setting the Battery Parameters
9.4.4.1 Setting Lithium Ion Battery Parameters
This function supports settings through the SolarGo app or LCD screen.
Method I: Setting via SolarGo APP
Step 1: Enter the parameter setting interface through Home > Settings > Advanced
Settings > Battery Function Settings.
Step 2: Enter the parameters and tap . The parameters are set successfully.
Number
Parameter
Description
1
Max. Charging Current
Set the maximum charging current based on actual
needs.
2
Max. Discharging
Current
Set the maximum discharging current based on actual
needs.
3
SOC Protection
Start battery protection when the battery capacity is
lower than the Depth of Discharge.
4
Depth of
discharge(on-grid)
Indicates the depth of discharge of the battery when
the inverter is on-grid or off-grid.
5
Depth of
discharge(off-grid)
6
Backup SOC Holding
The battery will be charged to preset SOC protection