182
F41:Generator
multiplexing port
overload
connected to the
generator is too
large, and the
current or power
of the GEN port
exceeds the
requirements
specified in the
specification.
2. The short circuit on
the back-up side
leads to the
current of the
generator port
exceeding the
requirements
specified in the
specifications.
3. When used as a
high-load port, the
high load exceeds
the requirements
specified in the
specifications.
port, immediately stop the operation
of the generator, check whether the
line is properly connected, and
confirm whether the parameters such
as output voltage, current, and power
on the back-up side exceed the
parameter requirements of the
specification. If the cable is not
properly connected, check and
reconnect it. If the parameters exceed
the requirements of the specifications,
reset the parameters according to the
requirements. If the circuit is intact
and the parameter settings are within
the specified range, but the problem
persists, please contact your dealer or
after-sales service center.
2. When the port is connected to a
heavy load, turn off the heavy load,
check if the line is properly connected,
and confirm if the load exceeds the
requirements of the specification. If
the cable is not properly connected,
check and reconnect it. If the load
exceeds the requirements in the
specification, reduce the load. If the
cables are well connected and the
load does not exceed the
specifications, and the fault still exists,
please contact your dealer or after-
sales service center.
38
AFCI Fault/
F42:DC Arc Fault
1. The connection of
DC string terminals
is not firm.
2. The DC cable
wiring is damaged.
Please check if the component
connection cables are correctly connected
according to the wiring requirements in
the quick installation manual.
39
Communication
indicator of the
inverter and Ezlink
indicator in error
Ezlink connection
failed
1. Check whether the WiFi signal is
normal. If it is not, check whether the
router works well.
2. Check whether Ezlink obtains IP