201
Application Method
On-grid/On-grid + Back-up/Back-up
Scalability
Supports up to 30 in parallel connection(150kWh)
(Hand-in-hand/Busbar connection)
Mounting Method
19-inch standard rack/floor mounted, wall-mounted
Cycle Efficiency
*1
≥96%
Cycle Life
600025℃±2℃,0.2C70%EOL
Warranty
*4
10 years
Standard
and
Certification
Safety
IEC62619IEC63056N140
EMC
EN IEC61000-6-1EN IEC61000-6-2EN IEC61000-
6-3EN IEC61000-6-4
Transportation
UN38.3ADR
Environment
ROHSREACH
*1: Test conditions: 100% DOD, 0.2C charge & discharge at 25°C± 2 ℃,at the beginning of life.
*2: Max. charge / discharge current may be variant with different inverter models
*3: Recommend/Max. Charging/Discharging Current/ Nominal/Max. Power* derating will occur
related to temperature and SOC.
*4: The warranty is due whichever reached first of warranty period or energy throughput.
LX U5.4-20
Technical Parameters
LX U5.4-20
2* LX U5.4-20
3* LX U5.4-20
Usable energy (kWh)
* 1
5.4
10.8
16.2
Cell Type
LFPLiFePO
4
Nominal Voltage (V)
51.2
Cell Configuration
16S1P
16S2P
16S3P
Nominal Voltage
51.2
Operating Voltage Range (V)
47.5~57.6
Nominal Charge/Discharge Current (A)
*2
50
100
Nominal Power (kW)
*2
2.56
5.12
Short-Circuit Current
2.323kA@1.0ms
Communication
CAN, RS485