the after-sales service center to confirm the installation
and application environment of the inverters to ensure
stable operation of the system.
Requirements for parallel system:
The software version of all inverters in the system
is the same.
The ARM software version of the inverter is 08
(415) and above.
The DSP software version of the inverter is
00(2525) and above.
Battery of different models cannot be mix used.
LX A5.0-10: The nominal charging and discharging
current of a single battery is 60A; a maximum of 15
batteries can be connected in parallel in one system.
LX A5.0-30: The nominal charging current of a single
battery is 60A, and the discharging current is 100A; the
maximum continuous charging current is 90A; the
maximum continuous discharging current is 150A. A
maximum of 30 batteries can be connected in parallel
in one system.
The maximum discharge current of a single battery is 50A;
A maximum of 6 batteries can be connected in parallel in
one system.
The nominal charging current of a single battery is 60A,
and the discharging current is 100A; the maximum
continuous charging current is 90A; the maximum
continuous discharging current is 100A. A maximum of 30
batteries can be connected in parallel in one system.
Supports connection to lead-acid batteries of AGM,
GEL, and Flooded types.
The number of batteries that can be connected in series
is calculated based on the voltage of lead-acid
batteries, and the total voltage of batteries connected
in series is not allowed to exceed 60V.
BCB-11-WW-0
BCB-22-WW-0
BCB-32-WW-0
BCB-33-WW-0
When the charging and discharging current between
the battery and the inverter is less than 160A, it
supports direct connection between battery and
inverter without using a busbar. For example: It
supports connecting GW8000-ES-C10 to LX A5.0-30