without using a busbar. For detailed battery wiring
methods, please refer to 6.6 Connecting Battery
Cables.
When the charging and discharging current between
battery and inverter is ≥160A, a busbar or busbar box
must be used to connect the inverter. (Current M x
IBat rated. (M: The quantity of batteries connected in
parallel in the system, IBat rated: The rated current of
the battery).
BCB-11-WW-0:
Used with LX A5.0-10, the battery system
supports a maximum working current of 360A,
working power of 18kW, and can connect to a
maximum of 3 inverters, and 6 batteries.
BCB-22-WW-0:
Used with LX A5.0-10, the battery system
supports a maximum working current of 720A,
working power of 36kW, and can connect to a
maximum of 6 inverters, and 12 batteries.
Used with LX A5.0-30, the battery system
supports a maximum working current of 720A,
working power of 36kW, and can connect to a
maximum of 6 inverters, and 6 batteries.
BCB-32-WW-0:
Used with LX A5.0-10, the battery system
supports a maximum working current of 720A,
working power of 36kW, and can connect to a
maximum of 6 inverters, and 15 batteries.
Used with LX A5.0-30, the battery system
supports a maximum working current of 720A,
working power of 36kW, and can connect to a
maximum of 6 inverters, and 15 batteries.
Used with LX U5.0-30, the battery system
supports a maximum working current of 720A,
working power of 36kW, and can connect to a
maximum of 6 inverters, and 8 batteries.
BCB-33-WW-0
Used with LX U5.0-30, the battery system
supports a maximum working current of 720A,
working power of 36kW, and can connect to a