9. Electrical connection
DANGER
Electric shock
Death or serious personal injury
Switch off the power supply to the
motor and to the signal relays. Wait at
least 5 minutes before you make any
connections in the terminal box. Make
sure that the power supply cannot be
switched on accidentally.
DANGER
Electric shock
Death or serious personal injury
Check that the supply voltage and
frequency correspond to the values
stated on the nameplate.
If the power cable is damaged, it must be replaced by
the manufacturer, the manufacturer's service partner
or a similarly qualified person.
The user or the installer is responsible for correct
earthing and protection according to local regulations.
All operations must be carried out by a qualified
electrician.
9.1 Protection against electric shock,
indirect contact
WARNING
Electric shock
Death or serious personal injury
Connect the motor to protective earth
and provide protection against indirect
contact in accordance with local
regulations.
Protective earth conductors must always have a
yellow and green, PE, or yellow, green and blue,
PEN, colour marking.
9.1.1
Protection against mains voltage transients
The motor is protected against mains voltage
transients in accordance with EN 61800-3.
9.1.2
Motor protection
The motor requires no external motor protection. The
motor incorporates thermal protection against slow
overloading and blocking.
9.2
Cable requirements
9.2.1 Cable cross-section
DANGER
Electric shock
Death or serious personal injury
Always comply with local regulations
as to cable cross-sections.
1 x 200-230 V
Power
[kW]
Conductor
type
Cross section
[mm
2
]
[AWG]
0.25 - 1.5
Solid 1.5 - 2.5 16-12
Stranded 1.5 - 2.5 16-12
3 x 380-500 V
Power
[kW]
Conductor
type
Cross section
[mm
2
]
[AWG]
0.25 - 2.2
Solid 1.5 - 10 16-8
Stranded 1.5 - 10 16-8
3.0 - 11
Solid 2.5 - 10 14-8
Stranded 2.5 - 10 14-8
3 x 200-240 V
Power
[kW]
Conductor
type
Cross section
[mm
2
]
[AWG]
1.1 - 1.5
Solid 1.5 - 10 16-8
Stranded 1.5 - 10 16-8
2.2 - 5.5
Solid 2.5 - 10 14-8
Stranded 2.5 - 10 14-8
9.2.2 Conductors
Type
Stranded or solid copper conductors.
Temperature rating
Temperature rating for conductor insulation: 60 °C
(140 °F).
Temperature rating for outer cable sheath: 75 °C
(167 °F).