Signal
range
[V, mA]
Actual value
Sensor
min
Sensor
max
0-10 V 0 V 10 V
0-20 mA 0 mA 20 mA
4-20 mA 4 mA 20 mA
The reading is a percentage of the range between
sensor
min
and sensor
max
.
Resulting setpoint
Signal
range
[V, mA]
Resulting setpoint
[%]
0 100
0-10 V 0 V 10 V
0-20 mA 0 mA 20 mA
4-20 mA 4 mA 20 mA
The reading is a percentage of the external setpoint
range.
Motor load
Signal
range
[V, mA]
Motor load
[%]
0 100
0-10 V 0 V 10 V
0-20 mA 0 mA 20 mA
4-20 mA 4 mA 20 mA
The reading is a percentage of the range between 0
and 200 % of the maximum permissible load at the
actual speed.
Motor current
Signal
range
[V, mA]
Motor current
[%]
0 100 200
0-10 V 0 V 5 V 10 V
0-20 mA 0 mA 10 mA 20 mA
4-20 mA 4 mA 12 mA 20 mA
The reading is a percentage of the range between 0
and 200 % of the rated current (I
N
).
Limit 1 exceeded and Limit 2 exceeded
Signal
range
[V, mA]
Limit-exceeded function
Output not
active
Output active
0-10 V 0 V 10 V
0-20 mA 0 mA 20 mA
4-20 mA 4 mA 20 mA
The Limit-exceeded function is typically used for
monitoring of secondary parameters in the system. If
the limit is exceeded, an output, warning or alarm is
activated.
Flow rate
Signal
range
[V, mA]
Flow rate
[%]
0 100 200
0-10 V 0 V 5 V 10 V
0-20 mA 0 mA 10 mA 20 mA
4-20 mA 4 mA 12 mA 20 mA
The reading is a percentage of the range between 0
and 200 % of the nominal flow.
Factory setting
See section Factory settings.
Related information
9.5.1 Connection terminals, advanced functional
module, FM 300
35. Factory settings
17.17
Controller (Controller settings)
Pump variant
Controller
(Controller settings)
TPE3, TPE3 D
TPE2, TPE2 D
The pumps have a factory setting of gain, K
p
and
integral time, T
i
.
However, if the factory setting is not the optimum
setting, you can change the gain and the integral
time:
Set the gain within the range from 0.1 to 20.
Set the integral time within the range from 0.1 to
3600 seconds.
If you select 3600 seconds, the controller
functions as a P controller.
Furthermore, you can set the controller to inverse
control.