13.1 Setpoint setting
Set the desired setpoint of the pump by pressing
or . The light fields on the control panel will
indicate the setpoint set.
13.1.1 Pump in differential-pressure control mode
The following example applies to a pump in an
application where a pressure sensor gives a feedback
to the pump. If you retrofit the sensor to the pump, set
it up manually as the pump does not automatically
register a connected sensor.
The figure below shows that the light fields 5 and 6
are activated, indicating a desired setpoint of 3 m with
a sensor measuring range from 0 to 6 m. The setting
range is equal to the sensor measuring range.
0
6
3
m
TM057958
Setpoint set to 3 m, differential-pressure control
13.1.2 Pump in constant-curve control mode
In constant-curve control mode, the pump
performance will lie between the maximum and
minimum curve of the pump.
H
Q
Max.
Min.
TM054895
Pump in constant-curve control mode
Setting to maximum curve:
Press continuously to change over to the
maximum curve of the pump. The top light field
flashes. When the top light field is on, press
for
3 seconds until the light field starts flashing.
To change back, press
continuously until the
desired setpoint is indicated.