17.46 Assisted pump setup
Pump variant Assisted pump setup
TPE3, TPE3 D
TPE2, TPE2 D
The menu guides you through the following:
Setting of pump
Selection of control mode. See section Control
mode.
Configuration of feedback sensors.
Adjusting the setpoint. See section Setpoint.
Controller settings. See
section "Controller"("Controller settings").
Summary of settings.
Example of how to use the Assisted pump setup
for setting up the pump to constant pressure:
Grundfos GO
1. Open the Assist menu.
2. Select Assisted pump setup.
3. Select the control mode "Constant pressure".
4. Read the description of this control mode.
5. Select which analog input to use as sensor input.
6. Select sensor function according to where the
sensor is installed in the system. See figure
Overview of sensor locations in section Analog
inputs.
7. Select electrical input signal according to the
sensor specifications.
8. Select measuring unit according to the sensor
specifications.
9. Set the minimum and maximum sensor values
according to the sensor specifications.
10. Set the desired setpoint.
11. Set the controller settings K
p
and T
i
. See the
recommendations in
section "Controller"("Controller settings").
12. Type the pump name.
13. Check the summary of settings and confirm them.
Advanced control panel
1. Open the Assist menu.
2. Select Assisted pump setup.
3. Select the control mode Const. pressure.
4. Select which analog input to be used as sensor
input.
5. Select the measured parameter to be controlled.
See figure Overview of sensor locations in section
Analog inputs.
6. Select measuring unit according to the sensor
specifications.
7. Set the minimum and maximum sensor values
according to the sensor specifications.
8. Select electrical input signal according to the
sensor specifications.
9. Set the setpoint.
10. Set the controller settings K
p
and T
i
. See
recommendations in
section "Controller"("Controller settings").
11. Check the summary of settings and confirm them
by pressing [OK].
Related information
17.2 Setpoint
17.6 Control mode
17.10 Analog inputs
17.17 Controller (Controller settings)
17.47 Setup, analog input
Pump variant Setup, analog input
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in the advanced control
panel.
The menu guides you through the following:
Setup, analog input
Analog inputs 1 to 3. See section Analog inputs.
Pt100/1000 input 1 and 2. See section
Pt100/1000 inputs.
Adjusting the setpoint. See section Setpoint.
Summary.
Related information
17.2 Setpoint
17.10 Analog inputs
17.12 Pt100/1000 inputs
75
English (GB)