Controller settings
For recommended controller settings, see the section
on the controller (controller settings).
Related information
17.17 Controller (Controller settings)
17.7 Proportional-pressure setup
Pump variant Proportional-pressure setup
TPE3, TPE3 D
TPE2, TPE2 D -
Control-curve function
You can set the curve either to quadratic or linear.
Zero-flow head
You can set this value in % of the setpoint. With a
setting of 100 %, the control mode is equal to
constant differential pressure.
17.8 FLOWLIMIT
Pump variant FLOWLIMIT
TPE3, TPE3 D
TPE2, TPE2 D -
FLOWLIMIT
Enable the FLOWLIMIT function.
Set the FLOWLIMIT.
H
Q
Q
max
Q
max
Q
limit
25 %
90 %
1
TM057908
FLOWLIMIT
Pos. Description
1 Setting range
You can combine the FLOWLIMIT function with the
following control modes:
Prop. pressure
Con. diff. press.
Con. diff. temp.
Const. temp.
Const. curve.
51
English (GB)