Pos. Description
A Setpoint influence [%]
B External input
17.20 Predefined setpoints
Pump variant Predefined setpoints
TPE3,TPE3 D ●
TPE2,TPE2 D ●
You can set and activate seven predefined setpoints
by combining the input signals to digital inputs 2, 3
and 4 as shown in the table below.
Set the digital inputs 2, 3 and 4 to "Predefined
setpoints" if all seven predefined setpoints are to be
used. You can also set one or two of the digital inputs
to "Predefined setpoints" but this will limit the number
of predefined setpoints available.
Digital inputs
Setpoint
2 3 4
0 0 0 Normal setpoint or stop
1 0 0 Predefined setpoint 1
0 1 0 Predefined setpoint 2
1 1 0 Predefined setpoint 3
0 0 1 Predefined setpoint 4
1 0 1 Predefined setpoint 5
0 1 1 Predefined setpoint 6
1 1 1 Predefined setpoint 7
0: Open contact
1: Closed contact
Example
The figure below shows how you can use the digital
inputs to set seven predefined setpoints. Digital input
2 is open and digital inputs 3 and 4 are closed. If you
compare with the table above, you can see that
"Predefined setpoint 6" is activated.