Example
The function is to monitor the outlet pressure of a
pump. If the pressure is below 5 bar for more than 5
seconds, a warning must be given. If the outlet
pressure is above 7 bar for more than 8 seconds, you
must reset the warning.
1
2
4
4
5
6
3
A
T
TM064603
Limit exceeded (example)
Pos. Setting parameter Setting
1 Measured Outlet pressure
2 Limit 5 bar
3 Hysteresis band 2 bar
4 Limit exceeded when Below limit
5 Detection delay 5 seconds
6 Resetting delay 8 seconds
A
Limit-exceeded function
active
-
- Action Warning
Factory setting
See section Factory settings.
Related information
17.15 "Signal relays 1 and 2" (Relay outputs)
35. Factory settings
17.23
Pulse flowmeter setup
Pump variant Pulse flowmeter setup
TPE3, TPE3 D
TPE2, TPE2 D
You can connect an external pulse flowmeter to one
of the digital inputs in order to register the actual and
accumulated flows. Based on this, you can also
calculate the specific energy.
To enable a pulse flowmeter, set one of the digital
inputs to Accumulated flow and set the pumped
volume per pulse. See section Digital inputs.
Factory setting
See section Factory settings.
Related information
17.13 Digital inputs
35. Factory settings