17.6.2 FLOWADAPT
Pump variant FLOWADAPT
TPE3, TPE3 D ●
TPE2, TPE2 D -
When you select FLOWADAPT, the pump runs
AUTOADAPT and ensures that the flow never
exceeds the entered FLOWLIMIT value.
The setting range for FLOWLIMIT is 25 to 90 %, of
the maximum flow rate of the pump.
The factory setting of the FLOWLIMIT is the flow rate
where the AUTOADAPT factory setting meets the
maximum curve. See figure FLOWADAPT.
Do not set the FLOWLIMIT lower than the sized duty
point.
H
Q
Q
max
25 %
90 %
H
auto_min
H
fac
Q
fac
1
TM057912
FLOWADAPT
Pos. Description
1 Setting range
17.6.3 Proportional pressure
Pump variant Proportional pressure
TPE3, TPE3 D ●
TPE2, TPE2 D -
The head of the pump is reduced at decreasing water
demand and increased at rising water demand. See
the figure Proportional pressure.
This control mode is especially suitable in systems
with relatively large pressure losses in the distribution
pipes. The head of the pump increases proportionally
to the flow in the system to compensate for the large
pressure losses in the distribution pipes.
The setpoint can be set with an accuracy of 0.1
metre. The head against a closed valve is half the
setpoint. The setting range is between 25 % and 90
% of maximum head.
For more information about settings, see section on
proportional-pressure setup.
TM057909
Proportional pressure
Example
• Factory-fitted differential-pressure sensor.
TM057880
Proportional pressure
Controller settings
For recommended controller settings, see section on
the controller (controller settings).
Related information
17.7 Proportional-pressure setup
17.17 Controller (Controller settings)